CCI-000972
CCI-000972 Definition
The organization defines acceptable temperature and humidity levels to be maintained within the facility where the information system resides.
Status | |
Type | CheckType.policy |
Master Assessment Datasheet
Implementation Guidance
DoD has defined the acceptable levels as for commercial grade information systems: 64.4 – 80.6 degrees F; 45% – 60% Relative Humidity; Dew Point 41.9 ° – 59°F; measured at the air intake inlet of the IT equipment casing; for other systems, levels within manufacturer specifications.
Validation Procedures
The organization being inspected/assessed is automatically compliant with this CCI because they are covered at the DoD level. DoD has defined the acceptable levels as for commercial grade information systems: 64.4 – 80.6 degrees F; 45% – 60% Relative Humidity; Dew Point 41.9 ° – 59°F; measured at the air intake inlet of the IT equipment casing; for other systems, levels within manufacturer specifications.
Compelling Evidence
Automatically Compliant